ENGINEERING TOOLS / ELECTRICITY

Three-Phase Power Calculator

Electrical parameters
Power results
Real power—
Apparent power—
Line current—
Reactive power magnitude—
Energy consumption and cost
Daily energy—
Monthly energy (30 days)—
Daily cost—
Monthly cost (30 days)—
Annual cost (365 days)—

Balanced, sinusoidal, steady-state loads only. Energy estimates assume constant load and daily runtime. Costs exclude demand charges, taxes and fixed fees. Currency follows your input rate. Not a conductor-sizing or electrical safety tool.

Need measured rather than estimated power? Explore the Eyedro 3-Phase Energy Meter.

Calculate three-phase real power (kW), apparent power (kVA), line current (amps), energy consumption and electricity costs. Enter your electrical system values below to estimate power for balanced three-phase loads.

How to calculate three-phase power

For a balanced three-phase electrical load, calculate real power using the line-to-line RMS voltage, line RMS current and power factor. The calculator above converts between current, real power and apparent power and estimates electricity consumption over time.

Real power is the rate of energy transfer to the load, measured in kilowatts (kW). Apparent power, measured in kilovolt-amperes (kVA), represents the product of RMS voltage and current with the three-phase factor included. Power factor is the ratio of real to apparent power.

Three-phase power formulas

MeasurementFormula
Real power (kW)√3 × V × I × PF / 1000
Apparent power (kVA)√3 × V × I / 1000
Current from kW (A)1000 × kW / (√3 × V × PF)
Current from kVA (A)1000 × kVA / (√3 × V)
Reactive power magnitude (kvar)√(kVA² − kW²)
Energy (kWh)kW × hours
Energy costkWh × electricity rate

V is line-to-line RMS voltage, I is line RMS current and PF is the dimensionless power factor. √3 is approximately 1.732. These formulas assume balanced sinusoidal loads; the reactive power formula does not distinguish inductive from capacitive loads.

How to convert three-phase amps to kW

Multiply the line-to-line voltage by the line current, power factor and √3, then divide by 1,000. For example, a 480 V load drawing 50 A at a power factor of 0.90 consumes approximately 37.41 kW, with an apparent power of 41.57 kVA.

Use the actual measured power factor rather than assuming unity power factor for motors, compressors or other reactive equipment.

How to convert three-phase kW to amps

Divide the real electrical input power in watts by √3 × line-to-line voltage × power factor. A 30 kW electrical load at 480 V and 0.90 power factor draws approximately 40.09 A per line when balanced.

If a motor nameplate specifies mechanical output power rather than electrical input power, account for motor efficiency first: electrical input kW = mechanical output kW / efficiency. Nameplate estimates are not a substitute for measured current or electrical design requirements.

Three-phase power calculation examples

Voltage (V)Current (A)PFReal power (kW)
208200.906.48
240300.9011.22
400500.9031.18
480500.9037.41
6001000.9598.73

All examples use balanced loads and line-to-line voltage. For the 480 V example, eight operating hours at constant load correspond to approximately 299.30 kWh and $44.89 at $0.15/kWh. Thirty identical operating days cost approximately $1,346.84 in energy charges, before demand charges and other fees.

Balanced versus unbalanced three-phase loads

The √3 formula applies when the three phases are balanced and sinusoidal. It can be used for balanced Wye and Delta systems when the inputs are line-to-line voltage and line current, not phase voltage or branch current.

In an unbalanced system, current, voltage or power factor may differ by phase. A single current reading or a simple average is not sufficient to determine real power accurately. Use a measurement method appropriate to the wiring topology, such as the sum of simultaneous phase power measurements for a four-wire Wye system or an appropriate wattmeter method for a three-wire system.

Variable-frequency drives and nonlinear loads may introduce harmonics. The calculator does not model harmonic distortion or transient behavior. Use compatible metering hardware for actual measurements. Read our three-phase power monitoring guide for more information.

Calculating versus monitoring actual electricity consumption

Power calculations are useful for planning, comparing equipment and estimating costs, but they rely on input assumptions. A machine may operate at different loads throughout a shift, and its power factor can change over time. Energy consumption is the integral of real power over time, not simply a nameplate rating multiplied by operating hours.

Continuous monitoring can reveal idle consumption, changing load profiles and demand peaks. A utility may bill peak demand using a defined averaging interval, so energy cost alone is not the full electricity bill.

Eyedro’s commercial energy monitoring solutions and MyEyedro Cloud help businesses track measured consumption and analyze historical usage instead of relying exclusively on estimates.

Frequently asked questions

Why is √3 used in three-phase power calculations?

In a balanced sinusoidal three-phase system, the phases are separated by 120 degrees. Combining the three phase powers and expressing them using line-to-line voltage and line current produces the √3 factor.

Does the calculator work for Wye and Delta?

Yes, for balanced sinusoidal systems using line-to-line voltage and line current. It is not intended for unbalanced high-leg Delta systems or other loads that cannot be represented by a single set of balanced inputs.

What power factor should I use?

Use measured true power factor where available. A value of 1 represents unity power factor. An assumed value such as 0.90 is illustrative and may not reflect your equipment.

What is the difference between kW and kVA?

kW is real power, while kVA is apparent power. Under the calculator assumptions, kW equals kVA multiplied by power factor.

How do I calculate three-phase kWh?

Multiply constant real power in kW by operating hours. For changing loads, integrate measured real power over time.

Can I use this calculator to size breakers or cables?

No. Electrical design requires additional information, applicable codes and qualified professional assessment. This tool estimates power and energy only.

Monitor three-phase power with Eyedro

Move beyond estimated electricity consumption with the Eyedro 3-Phase Energy Meter. Compatible models provide real-time electrical measurements for commercial and industrial applications. View measured energy consumption and historical trends using MyEyedro Cloud.

Verify voltage, frequency, topology and sensor compatibility before selecting a model. Installation must follow manufacturer instructions and applicable electrical safety requirements.